| Doctype | Test Report |
|---|---|
| Product line | openvvvf |
| Applies to | openvvvf-control-module, chassis-size-2 |
| Version | 0.1 |
| Date | 2026-09-26 |
| Description | Second SSO-latency execution on Gen7 size 2 at 49 V — gate-drive power kill (Path 2a) and gate-drive reset (Path 4) reach six-switch-open but initially with no firmware detection; gate-loss and torque-loss detectors were added fix-forward and both pathways retested to pass with correct flag words. |
| Test id | 21 |
| Nav order | 391 |
| Normative refs | OV-TEST-HW-SSO-LATENCY, OV-TEST-METHODOLOGY, OV-TEST-COVERAGE, OV-TEST-FAULT-INJECTION |
SSO Gate-Drive Kill Pathways — Gen7 Size 2, Low Bus
This report continues OV-TEST-HW-SSO-LATENCY on the Gen7 size 2 assembly at 49.3 V, covering Path 2a (gate-drive power kill) and Path 4 (GATE_DRIVE_RESET assertion) — the two gate-endpoint pathways actuatable from the test build. Injections were actuated through the real hardware enable/reset lines via two firmware injection hooks added for this campaign (gatepwr, gaterst), so the endpoint hardware (gate-driver supply rail, driver reset input) is genuinely exercised; no physical harness modification was required.
First-pass result: both pathways physically reached six-switch-open, but with an empty fault flag word — a fail against the plan's detection requirement. Per the campaign's fix-forward rule, detection was implemented in firmware (gate-loss and torque-loss detectors) and both injections retested to pass with correct flag words, bounded currents, and blocked-then-clean re-enable. As-found and as-left results are both recorded below.
Test setup
- DUT: OpenVVVF Gen7 control module + C2 power stage, 200 V class variant.
- Firmware: RTE generated build, graph
foc_demo, hashbd5390d76c425eb1(82 nodes) throughout. Base for injections: commitbc02138(test 20 fix set); detection retests: commita8b223b(adds the two detectors and the injection hooks; 5 files, +116). Both on branchcoproc-flash-fixes, pushed. - Injection hooks (new shell commands, bypass the fault manager by design):
gatepwr <0|1>— drives the gate-driver power-enable line directly (Path 2a endpoint).gaterst <0|1>— asserts/releases the gate-driver reset line directly (Path 4 endpoint).- Machine / load: Zero ZF75-10 PMSM, coupled, unloaded. Bus: 49.3 V bench supply.
- Instrumentation: RTE Studio telemetry (~132 Hz); firmware 5 kHz spike capture; oscilloscope on one phase lead (operator-monitored, not archived).
Test conditions
| Run | Pathway | Injection | Operating point | Detection (as found) | Detection (as left) | Result |
|---|---|---|---|---|---|---|
| 1 | 2a gate power kill | gatepwr 0 while RUNNING |
−15.2 A, −1800 RPM | None — flags 0x00000000, RUNNING, MOE set, PI wound to voltage rail |
GateDriver fault 0x00000001 in ~0.2–0.3 s |
Fail → Pass |
| 2 | 4 reset assert | gaterst 1 while RUNNING |
−10.6 A, −2188 RPM | None — no pin observable at all (gate_ready stays Y) |
TorqueLoss fault 0x80000000 in ~160 ms |
Fail → Pass |
| 3 | 4 reset release (as found) | gaterst 0 under wound-up PI |
— | — | — | Surge → software OC fault (finding) |
| 4 | Regression | normal run, starts/stops, AWD trip | −15 A, 20 s | — | no false trips; AWD still 0x00400000 only |
Pass |
Procedure
- Preconditions: bus 49.3 V, telemetry streaming, no faults,
hwocset 0(ADC watchdog disarmed for these runs). - Established the operating point (
control start,var set IqVar -15, ~10 s settle). - Run 1 (Path 2a):
gatepwr 0while running; recorded currents, state, flags,gate_ready,gate_fault, spike capture. Recovery:control stop→gatepwr 1→ restart attempt. - Run 2 (Path 4):
gaterst 1while running (30 s window); same recording. Thengaterst 0— which produced the release-surge finding (run 3). - Fix-forward: implemented detection (below), reflashed, repeated runs 1–2 with the full recovery sequence (stop → restore →
fault clear→ restart). - Run 4 (regression): 20 s at −15 A, standstill start/stop cycles, and one
hwocset 8+IqVar −40ADC-watchdog trip to confirm no interaction with the new detectors.
Electrical results
As found (commit bc02138):
- Both injections physically reached SSO: phase current collapsed within one exported sample (≤ 100 ms export bound; physically immediate freewheel decay) and the machine coasted to rest. No spike on the cut itself (recorder held only pre-cut waveform ≤ 25 A).
- Detection: none on either pathway.
fault_flags_hexstayed0x00000000, supervisor RUNNING,pwm_moe= 1 (TIM1 switching into dead gates), PI wound to the voltage limit (vq_req≈ −27 V against iq ≈ 0).gate_fault(/FLT) never asserted.gate_readyfell ~0.1 s after the power cut only; the reset assertion had no pin-level observable at all. - Release surge (Path 4): releasing reset after 2 s of assertion reconnected the gates to a fully wound-up PI — a real current surge tripped software PhaseOvercurrent (>500 A processed × 3 samples). Latched fault required
fault clear, as designed, and recovery was clean.
As left (commit a8b223b):
- Path 2a:
gatepwr 0at −13.8 A →GateDriverfault (flag0x00000001, exactly one bit) raised ~0.2–0.3 s after the cut (gate_ready debounce 100 ms + service latency; ≈ 20–30 control cycles), standard safety sequence (PWM break, driver reset, power off), SSO. Recovery: stop →gatepwr 1(gate_readyback within 1 s) →fault clear critical→ clean restart at −14.9 A. - Path 4:
gaterst 1at −15 A / −2193 RPM →TorqueLossfault (flag0x80000000, exactly one bit) in ~160 ms (150 ms debounce + ≤ 10 ms service; ≈ 16 control cycles), safety sequence, currents bounded ≤ 20.4 A (the pre-injection level). The detector firing during assertion defused the release surge: stop →gaterst 0→fault clear critical→ clean restart, no overcurrent event. - Detection design: both detectors live in the supervisor service loop (graph control only). Gate-power loss:
gate_readylow, debounced 100 ms, only while actuation is active → existingGateDriverfault source. Dead gates / torque loss: newTorqueLosssource (bit 31) — EMA(|iq|, α=0.2 @ 100 Hz) < 4 A while |iq_ref| ≥ 5 A and |vq_req| ≥ 90 % of the voltage limit, debounced 150 ms. The EMA is required because post-cut iq bounces above 2 A in ~50 % of samples; measured EMA|iq| ≈ 1.7 A collapsed vs ≥ 10.5 A in real operation (>2× margin both ways). vq-clamp alone is never used as a discriminator — this bench's normal operating point is itself voltage-limited at −10.5 A. Edge guards: no firing at IDLE (rail legitimately off), no re-raise afterfault clearwhile power is still off, no retrigger from the safety sequence's own power cut. - Regression: 20 s at −15 A plus start/stop cycles — zero detector activity, flags
0x00000000throughout. Thehwocset 8+ −40 A watchdog trip still producesAdcWatchdogonly (0x00400000) with the immediate TIM1 break — the supervisor's fault transition gates both detectors within one 100 Hz tick, long before their debounces complete.
Thermal results
Not applicable — short runs at ≤ 15 A; no meaningful temperature rise.
Telemetry overview
Per-run full telemetry histories (CSV, long format signal,time_s,value) are filed as artifacts below: as-found runs, release-surge event, detection retests, and the regression run. Flag words quoted above are from live snapshots at each event (fault_flags_hex is transition-logged and does not appear in the 128 Hz history exports).
Observations
- Fail-as-found, fix-forward, retest-to-pass — the as-found state (SSO without detection) failed the plan's flag-word acceptance criterion on both pathways; the detection design above is the corrective action, verified on the same bench in the same session.
- No pin observable for Path 4: the gate-driver /FLT output does not assert for a reset assertion (rail stays up, driver ready), so reset-assertion detection is necessarily physiological (torque-loss). This also means a physical GATE_DRIVE_RESET fault (short to active) is now covered by the same detector.
- Detection latency vs budget: both detectors fire in ≤ 0.3 s of the injection — inside the 200 ms FSR-05 budget for the gate-loss path (~0.2–0.3 s measured; dominated by the 100 ms debounce plus rail-decay time for /RDY) and ~160 ms for torque loss. The physical SSO itself is immediate in both cases (passive freewheel decay); the measured latency is detection-and-latching, which is what sequences the controller to a clean, recoverable fault state. Debounce values are first-pass conservative choices; tightening them (or moving detection into the control ISR) is available if a future budget demands it.
- New fault source:
TorqueLoss(bit 31, Critical, "Gate Drive" category) is table-driven like existing sources —fault_active_names,fault clear TorqueLoss, and MCP/Studio discovery work unchanged. - Injection hooks are now permanent campaign tooling (
gatepwr,gaterst, plushwocsetfrom test 20); they bypass the fault manager by design and are labeled FAULT INJECTION in help. - Pathways still open: Path 2b (coprocessor gate-power path — coprocessor firmware in progress), Path 3 (3.3 V rail removal — needs a physical rig), Paths 5/6 (coprocessor watchdog/trigger — same dependency). Scope-captured sub-µs design-budget verification for Path 4 remains an optional refinement, not a pass/fail gate.
Conclusion
Pass (as left) for Pathways 2a and 4. Gate-drive power kill and gate-drive reset assertion both move the inverter to six-switch-open immediately and — after the fix-forward detection work — raise the correct single-bit fault word within ≤ 0.3 s, sequence the standard safety response, block re-enable until fault clear, and recover cleanly. The release-surge hazard found on Path 4 is eliminated by the same detectors. Combined with test 20 (gate-driver fault injection + ADC watchdog), four of the six FSR-05 SSO pathways now have measured low-bus evidence; the remainder are blocked on the coprocessor firmware and a 3.3 V rail rig.
Artifacts
As-found (pre-detection):
- Run 1 —
gatepwr 0cut at −15.2 A, no detection (CSV) · recovery (CSV) - Run 2 —
gaterst 1assertion at −10.6 A, no detection (CSV) · Run 3 — release surge → software OC fault (CSV)
As-left (with detection, commit a8b223b):